| General information |
| HW functional status |
FS01 |
| Firmware version |
V2.1.0 |
| ● FW update possible |
Yes |
| Product function |
| ● I&M data |
Yes; I&M0 to I&M3 |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated as of version |
V13 SP1 / - |
| ● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
| ● PROFIBUS as of GSD version/GSD revision |
V1.0 / V5.1 |
| ● PROFINET as of GSD version/GSD revision |
V2.3 / - |
| Operating mode |
| ● DI |
Yes |
| ● Counter |
Yes |
| ● Oversampling |
No |
| ● MSI |
Yes |
| Supply voltage |
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes |
| Input current |
| Current consumption, max. |
40 mA; 20 mA per group with 24 V DC supply |
| Power |
| Power available from the backplane bus |
1.1 W |
| Power loss |
| Power loss, typ. |
4.2 W |
| Digital inputs |
| Number of digital inputs |
32 |
| Digital inputs, parameterizable |
Yes |
| Source/sink input |
P-reading |
| Input characteristic curve in accordance with IEC 61131, type 3 |
Yes |
| Digital input functions, parameterizable |
| ● Gate start/stop |
Yes |
| ● Freely usable digital input |
Yes |
| ● Counter |
|
| — Number, max. |
2 |
| — Counting frequency, max. |
1 kHz |
| — Counting width |
32 bit |
| — Counting direction up/down |
Up |
| Input voltage |
| ● Rated value (DC) |
24 V |
| ● for signal "0" |
-30 to +5V |
| ● for signal "1" |
+11 to +30V |
| Input current |
| ● for signal "1", typ. |
2.5 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — parameterizable |
Yes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms |
| — at "0" to "1", min. |
0.05 ms |
| — at "0" to "1", max. |
20 ms |
| — at "1" to "0", min. |
0.05 ms |
| — at "1" to "0", max. |
20 ms |
| for interrupt inputs |
| — parameterizable |
Yes |
| for technological functions |
| — parameterizable |
Yes |
| Cable length |
| ● shielded, max. |
1 000 m |
| ● unshielded, max. |
600 m |
| Encoder |
| Connectable encoders |
| ● 2-wire sensor |
Yes |
| — permissible quiescent current (2-wire sensor), max. |
1.5 mA |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) |
Yes |
| Filtering and processing time (TCI), min. |
80 µs; At 50 μs filter time |
| Bus cycle time (TDP), min. |
250 µs |
| Interrupts/diagnostics/status information |
| Diagnostics function |
Yes |
| Alarms |
| ● Diagnostic alarm |
Yes |
| ● Hardware interrupt |
Yes |
| Diagnostic messages |
| ● Monitoring the supply voltage |
Yes |
| ● Wire-break |
Yes; to I < 350 µA |
| ● Short-circuit |
No |
| Diagnostics indication LED |
| ● RUN LED |
Yes; Green LED |
| ● ERROR LED |
Yes; Red LED |
| ● Monitoring of the supply voltage (PWR-LED) |
Yes; Green LED |
| ● Channel status display |
Yes; Green LED |
| ● for channel diagnostics |
Yes; Red LED |
| ● for module diagnostics |
Yes; Red LED |
| Potential separation |
| Potential separation channels |
| ● between the channels |
Yes |
| ● between the channels, in groups of |
16 |
| ● between the channels and backplane bus |
Yes |
| ● between the channels and the power supply of the electronics |
No |
| Isolation |
| Isolation tested with |
707 V DC (type test) |
| Standards, approvals, certificates |
| Suitable for safety functions |
No |
| Ambient conditions |
| Ambient temperature during operation |
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
0 °C |
| ● vertical installation, max. |
40 °C |
| Altitude during operation relating to sea level |
| ● Installation altitude above sea level, max. |
5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Decentralized operation |
| Prioritized startup |
Yes |
| Dimensions |
| Width |
35 mm |
| Height |
147 mm |
| Depth |
129 mm |
| Weights |
| Weight, approx. |
260 g |
| last modified: |
06/03/2019 |