e-Elit - juhtiv
elektri- ja automaatikatarvikute
online hulgimüük
Klienditeenindus E-R 9-17
Helista: +372 622 9119
Est En
Elit shopping basket
Tooteid: Maksumus:
0
€ 0,00
    search
Logi sisse
Kasutajatunnus/e-post:

Parool:

Näita kõiki kategooriaid
Ei leidnud sobilikku toodet?
Head pakkumised!
End Cover D-STTBS 2.5, 50pcs/pck, Phoenix
End Cover D-STTBS 2.5, 50pcs/pck, Phoenix



ProfiBus OLM/G12 V4.0 Optical Link Module, 1 RS485, 2 glass FOC interfaces (4 BFOC sockets), up to 2850m, signaling contact, measuring output
Pilt on illustreeriv
ProfiBus OLM/G12 V4.0 Optical Link Module, 1 RS485, 2 glass FOC interfaces (4 BFOC sockets), up to 2850m, signaling contact, measuring output
Kood: 6GK1503-3CB00
Hind (indikatiivne)
€ 751,42  /tk
Tootja :
Saadavus:
14 päeva
Kaal:
0.4358 kg/tk
Maht:
0.0013 m3/tk
Kogus (tk):
Plus sign Minus sign
 

 

ProfiBus OLM/G12 V4.0 Optical Link Module, 1 RS485 ˄2 glass FOC interfaces (4 BFOC sockets), up to 2850m, signaling contact ˄measuring output, Siemens

SIMATIC DP, interface DP/PA-Link and ET200M IM153-2 HF for extended temperature range for max. 12 S7-300 modules with redundancy capability, Timestamping suitable for isochronous mode New features: up to 12 modules can be used Slave Initiative for Drive ES and Switch ES Expanded quantity structure for HART auxiliary variables Operation of the 64-channel modules 32 signals / slot +++ Observe compatibility instructions in manual +++
General information
Product type designation IM 153-2 HF
Firmware version V6.0.0
Vendor identification (VendorID) 801Eh
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2,5 A
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Current consumption, max. 650 mA
Inrush current, typ. 3 A
I²t 0.1 A²·s
Output current
for backplane bus (5 V DC), max. 1.5 A
Power loss
Power loss, typ. 5.5 W
Address area
Addressing volume
● Inputs 244 byte
● Outputs 244 byte
Hardware configuration
Number of modules per DP slave interface, max. 12
Time stamping
Accuracy 1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules
Number of message buffers 15
Messages per message buffer 20
Number of stampable digital inputs, max. 128; Max. 128 signals/station; max. 32 signals/slot
Time format RFC 1119
Time resolution 0.466 ns
Time interval for transmitting the message buffer if a message is present 1 000 ms
Time stamp on signal change rising / falling edge as signal entering or exiting
Interfaces
Transmission procedure RS 485
PROFIBUS DP
● Node addresses 1 to 125 permitted
● automatic detection of transmission rate Yes
● Output current, max. 70 mA
● Transmission rate, max. 12 Mbit/s
● SYNC capability Yes
● FREEZE capability Yes
● Direct data exchange (slave-to-slave communication) Yes; as publisher with all IO, as subscriber with F-IO only
● Design of electrical connection of PROFIBUS interface 9-pin sub D
1. Interface
PROFIBUS DP slave
● GSD file SI05801E.GSG
● automatic baud rate search Yes
Protocols
Bus protocol/transmission protocol PROFIBUS DP to EN 50170
Potential separation
Potential separation exists Yes
Isolation
Isolation tested with Isolation voltage 500 V
Degree and class of protection
IP degree of protection IP20
Ambient conditions
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 3 000 m
Configuration
Configuration software
● STEP 7 Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight, approx. 360 g
last modified: 11/10/2018
 
 
Elit OÜ | e-post: elit@elit.ee | +372 622 9119 | 2021 ©


 
X
 
X